Low heat pump COP: the Vaillant flow sensor that read 1.5°C low

Low heat pump COP was the reason Heat Geek asked me to go and look at this job. The customer had spotted it too. They’d been keeping an eye on the figures and were keen to get it sorted.

Two Bluetooth pipe probes clipped to the flow and return inside the Vaillant outdoor unit
My Bluetooth probes on the flow and return inside the outdoor unit.

2.7 for heating on a system with everything going for it

It’s a 5kW Vaillant aroTHERM plus on underfloor heating. That should be a very, very efficient job. The day before I went, myVAILLANT Pro recorded 2.7 for heating and 1.6 for hot water. That’s absolutely nowhere near what I’d expect for that system.

I checked the underfloor heating first. It was balanced. The water was flowing round a bit too fast even though the pump was on the lowest setting already, so I slowed it down using the UFH flow setters. Then I put my Bluetooth probes on the flow and return pipes inside the heat pump and compared them with what the Vaillant controller was reading.

The return was about right. The flow was reading low.

My probes were showing about 3°C difference between flow and return. The Vaillant flow thermistor was reading about 1.5°C lower than my flow probe. With such a small temperature difference to start with, that’s a big error.

Here are the two screens I was looking at. They’re 85 seconds apart:

Flow and return readings before I changed the thermistor
ReadingMy Bluetooth probes Vaillant controller
Flow31.4°C29.77°C
Return28.6°C28.02°C
ΔT2.8°C1.75°C
Bluetooth probe display showing 31.4°C flow and 28.6°C return
09:14:36 · My probes: 31.4°C flow, 28.6°C return. ΔT 2.8°C.
Vaillant graph showing measured flow and return temperatures
09:13:11 · Vaillant: 29.77°C flow, 28.02°C return. ΔT 1.75°C. I’m comparing the measured flow temperature, not the flow target.

At one point during the test my probes showed a ΔT of about 3°C and the Vaillant was seeing about half of it. At the same flow rate, half the temperature difference means half the calculated heat output. So at that moment it was recording about half the COP it should have been recording.

I had a spare thermistor on the van

I fitted it and checked the flow temperature again. The new thermistor agreed with my Bluetooth probe and the COP on the Vaillant went up straight away.

I checked the next day and again a couple of days later. These are the readings before the repair and on 21 November:

Before repair: total 2.6, heating 2.7, hot water 1.6
Day before the repair: 2.6 overall, 2.7 for heating and 1.6 for hot water.
After repair: total 4.7, heating 4.7, hot water 4.1
21 November: 4.7 overall, 4.7 for heating and 4.1 for hot water.

It was around 6–8°C during the day and down to zero at night. I’m very happy with 4.7 for heating in that weather. What I fixed was the temperature reading. The old sensor had been undercounting the heat the unit was already putting into the house.